LECTURE NOTES
ON
ELECTRICAL INSTALLATION &
ESTIMATING
Mrs. Lipsarani Bagh
Lecturer, Electrical Engineering Department
GOVERNMENT POLYTECHNIC, SAMBALPUR
CAPTER-1
INDIAN ELECTRICITY RULES
1.1 Denions, Ampere, Apparatus, Accessible, Bare, cable, circuit, circuit breaker, conductor
voltage (low, medium, high, EH), live, dead, cut-out, conduit, system, danger, Installaon,
earthing system, span, volt, switch gear, etc.
1.2 General safety precauons, rule 29, 30, 31, 32, 33, 34, 35, 36, 40, 41, 43, 44, 45, 46.
1.3 General condions relang to supply and use of energy : rule 47, 48, 49, 50, 51, 54, 55, 56,
57, 58, 59, 60, 61, 62, 63, 64, 65, 66, 67, 68, 70.
1.4 OH lines : Rule 74, 75, 76, 77, 78, 79, 80, 86, 87, 88, 89, 90, 91
1.1 DEFINITIONS
AMPERE
Ampere is the unit of electric current in IS unit.
An ampere is a unit of measure of rate of electron ow in an electrical conductor. One
ampere of current represents one coulomb of electric charge charge(6.24x10
18
) moving a
specic point in one second.
APPARATUS
It is a technical equipment or machinery needed for a parcular acvity or purpose. OR
It is a set of materials or equipment designed for a parcular use. OR
Apparatusmeans electrical apparatus and includes all machines, ngs,
accessories and appliances in which conductors are used.
ACCESSIBLE
Accessible means easy to approach, reach, enter, speak with or use.
BARE
Bare means the conductor which is not covered with insulang materials.
CABLE
“Cablemeans a length of insulated single conductor. The conductor may be solid or stranded
, two no of more than two no and each provided with its own insulaon. Such insulated
conductor or conductors may or may not be provided with an overall mechanical protecve
covering.
CIRCUIT
“Circuitmeans an arrangement of conductor or conductors for the purpose
of conveying energy and forming a system or a branch of a system.
OR
Circuit is an interconnecon of electrical components and conductors which form a complete
path for the current to ow through it.
CIRCUIT BREAKER
“Circuit breakermeans a device which is capable of making and breaking the
circuit under all condions.
OR
A circuit breaker is an electrical protecve device which protect the circuit from damaged
caused by overcurrent, overload or short circuit by breaking the circuit.
CONDUCTOR VOLTAGE
It is the voltage/potenal dierence between any two conductor or voltage/potenal
dierence between any conductor and neutral.
Low voltage-voltage level below 250volt.
Medium voltage- voltage level between 250volt to 650volt.
High voltage-voltage level less than or equal to 33000volt.
Extra high voltage- Voltage level greater than 33000volt.
LIVE - Live term in electrical means electrically charged.
DEAD
“Deadmeans at or about earth potenal and disconnected from any live
System. The term “deadis used only with reference to current carrying parts when
these parts are not live.
CUT-OUT
“Cut-outmeans any appliance for automacally interrupng the
transmission of energy through any conductor when the current rises above a predetermined
amount.
CONDUIT
“Conduitmeans rigid or exible metallic tubing or mechanically strong and
re resisng non-metallic tubing into which a cable or cables may be drawn for the
purpose of aording it or for mechanical protecon.
SYSTEM
System means an electrical system in which all the conductors and
apparatus are electrically connected to a common source of electric supply.
VOLT
“Voltmeans a unit of electromove force and is the electric pressure,
which, when steadily applied to a conductor, the resistance of which is one ohm,
will produce a current of one amphere.
SWITCHGEAR
“Switchgearshall denote switches, circuit breakers, cut-outs and other
apparatus used for the operaon, regulaon and control of circuits
“Spanmeans the horizontal distance between two adjacent supporng
points of an overhead conductor.
INSTALLATION
“Installaonmeans any composite electrical unit used for the purpose of
generang, transforming, transming, converng, distribung or ulizing energy;
EARTHING SYSTEM
“Earthing systemmeans an electrical system in which all the conductors
are earthed
“Earthedor “connected with earthmeans connected with the general
mass of earth in such manner as to ensure at all mes an immediate discharge of
energy without danger
DANGER
“Dangermeans danger to health or danger to life or any part of body from
shock, burn or other injury to persons, or property, or from re or explosion,
aendant upon the generaon, transmission, transformaon, conversion,
distribuon or use of energy
LIGHTING ARRESTOR
“Lighng arrestormeans a device which has the property of diverng to
earth any electrical surge of excessively high amplitude applied to its terminals
and is capable of interrupng follow current if present and restoring itself thereaer
to its original operang condions.
1.2 General safety precauons
RULE 29-Construcon, installaon, protecon, operaon and maintenance of electric supply
lines and apparatus.
All electric supply lines and apparatus shall be of sucient rangs for
power, insulaon and of sucient mechanical strength. They shall be constructed, installed,
protected, worked and maintained in such a manner as to ensure safety of human beings,
animals and property.
The material and apparatus used shall conformed to have relevant specicaons as per
Bureau of Indian Standards.
RULE 30- Service lines and apparatus on consumer’s premises-
(1) The supplier shall ensure that all electric supply lines, wires, ngs and
apparatus belonging to him or under his control, which are on a consumer’s
premises, are in a safe condion and in all respects t for supplying energy and
the supplier shall take due precauons to avoid danger arising on such premises
from such supply lines, wires, ngs and apparatus.
(2) Service-lines placed by the supplier on the premises of a consumer which
are underground or which are accessible shall be so insulated and protected by
the supplier.
(3) The consumer shall, as far as circumstances permit, take precauons for
the safe custody of the equipment on his premises belonging to the supplier.
(4) The consumer shall also ensure that the installaon under his control is
maintained in a safe condion.
RULE 31- Cut-out on consumer’s premises
The supplier shall provide a suitable cut-out in each conductor of every
service-line other than an earthed or earthed neutral conductor or the earthed
external conductor of a concentric cable within a consumers premises, in an
accessible posion.
Where more than one consumer is supplied through a common service-line, each
such consumer shall be provided with an independent cut-out at the point of
juncon to the common service.
RULE-32. Idencaon of earthed and earthed neutral conductors and posion of
switches and cut-outs.
(1) An indicaon of a permanent nature shall be provided by the owner of the
earthed or earthed neutral conductor, or the conductor which is to be connected
there to, to enable such conductor to be disnguished from any live conductor.
(2) No cut-out, link or switch other than a linked switch arranged to operate
simultaneously on the earthed or earthed neutral conductor and live conductors
shall be inserted or remain inserted in any earthed or earthed neutral conductor of
a two wire-system or in any earthed or earthed neutral conductor of a mul-wire
system .
RULE-33. Earthed terminal on consumer’s premises-
(1) The supplier shall provide and maintain on the consumer’s premises for the
consumer’s use a suitable earthed terminal in an accessible posion at or near the
point of commencement of supply as dened under rule 58.
(2) The consumer shall take all reasonable precauons to prevent mechanical
damage to the earthed terminal and its lead belonging to the supplier.
1[(3) The supplier may recover from the consumer the cost of installaon of earthing.
RULE-34. Accessibility of bare conductors- Where bare conductors are used in a
building, the owner of such conductors shall-
(a) Ensure that they are inaccessible;
(b) Provide in readily accessible posion switches for rendering them dead
whenever necessary; and
(c) Take such other safety measures as are considered necessary by the
Inspector.
Rule-35. Danger Noces- The owner of every medium, high and extra-high voltage
installaon shall ax permanently in a conspicuous posion a danger noce in
Hindi or English and the local language of the district, with a sign of skull and
bones
RULE-36. Handling of electric supply lines and apparatus-
(1) Before any conductor or apparatus is handled adequate precauons shall
be taken, by earthing or other suitable means, to discharge electrically such
conductor or apparatus.
Every person who is working on an electric supply line or apparatus or both shall
be provided with tools and devices such as gloves, rubber shoes, safety belts,
ladders, earthing devices, helmets, line testers, hand lines and the like for
protecng him from mechanical and electrical injury. Such tools and devices shall
always be maintained in sound and ecient working condions:
(2) No person shall work on any live electric supply line or apparatus and no
person shall assist such person on such work, unless he is authorised in that
behalf, and takes the safety measures approved by the Inspector.
(3) Every telecommunicaon line on supports carrying a high or extra-high
voltage line shall, for the purpose of working there on, be deemed to be a high
voltage line.
RULE-37. Supply to vehicles, cranes, etc.
Every person owning a vehicle, travelling crane or the like to which energy is supplied from an
external source shall ensure that it is eciently controlled by a suitable switch enabling all
voltage to be cut o in one operaon and, where such vehicle, travelling crane or the like runs
on metal rails, the owner shall ensure that the rails are electrically connuous and earthed.
RULE-38. Cables for portable or transportable apparatus-
(1) Flexible cables shall not be used for portable or transportable motors,
generators, transformer recers, electric drills, electric sprayers, welding sets or
any other portable or transportable apparatus unless they are heavily insulated
and adequately protected from mechanical injury.
(2) Where the protecon is by means of metallic covering, the covering shall be
in metallic connecon with the frame of any such apparatus and earth.
(3) The cables shall be three core type and four-core type for portable and
transportable apparatus working on single phase and three phases supply
respecvely and the wire meant to be used for ground connecon shall be easily
idenable.
RULE-39. Cables protected by bituminous materials-
(a) Where the supplier or the owner has brought into use an electric supply line
(other than an overhead line) which is not completely enclosed in a connuous
metallic covering connected with earth and is insulated or protected in situ by
composion or material of a bituminous character-
(i) Any pipe, conduit or the like into which such electric supply line may have
been drawn or placed shall, unless other arrangements are approved by the
Inspector in any parcular case, be eecvely sealed at its point of entry into any
street box so as to prevent any ow of gas to or from the street box; and
(ii) Such electric supply line shall be periodically inspected and tested where
accessible, and the result of each such inspecon and test shall be duly recorded
by the supplier or the owner.
(2) It shall not be permissible for the supplier or the owner aer the coming into
force of these rules, to bring into use any further electric supply line as aforesaid
which is insulated or protected in situ by any composion or material known to be
liable to produce noxious or explosive gases on excessive heang.
RULE-40. Street boxes-
(1) Street boxes shall not contain gas pipes, and precauons shall be taken to
prevent, as far as reasonably possible, any inux of water or gas.
(2) Where electric supply lines forming part of dierent systems pass through
the same street box, they shall be readily disnguishable from one another and all
electric supply lines at high or extra-high voltage in street boxes shall be
adequately supported and protected to as to prevent risk of damage to or danger
from adjacent electric supply lines.
(3) All street boxes shall be regularly inspected for the purpose of detecng the
presence of gas and if any inux or accumulaon is discovered.
(4) The owners of all street boxes or pillars containing circuits or apparatus
shall ensure that their covers and doors are so provided that they can be opened
only by means of a key or a special appliance.
RULE-41. Disncon of dierent circuits-
The owner of every generang staon, substaon,
juncon-box or pillar in which there are any circuits or apparatus, whether
intended for operaon at dierent voltages or at the same voltage, shall ensure by
means of indicaon of a permanent nature that the respecve circuits are readily
disnguishable from one another.
RULE-42. Accidental charge-
The owners of all circuits and apparatus shall soarrange them that there shall be no danger of
any part thereof becoming accidentally charged to any voltage beyond the limits of voltage
for which they are intended.
Where A.C. and D.C. circuits are installed on the same support they shall be so
arranged and protected that they shall not come into contact with each other when
live.
RULE-43. Provisions applicable to protecve equipment-
(1) Fire buckets lled with clean dry sand ,re exngguishers must be kept in all generang
stson,enclosed sub-staons etc to exnguish re.
(2The re exnguishes shall be tested for sasfactory operaon at least once a year
and record of such tests shall be maintained.
(2) First-aid boxes or cupboards, conspicuously marked and equipped with
such contents as the State Government may specify, shall be provided and
maintained in every generang staon, enclosed sub-staon and enclosed switch
staon so as to be readily accessible during all working hours. All such boxes and
cupboards shall, except in the case of unaended sub-staons and switch
staons, be kept in charge of responsible persons who are trained in rst-aid
treatment and one of such person shall be available during working hours.
(3) Gas masks shall be provided conspicuously and installed and
maintained at accessible places in every generang staon with capacity of 5 MW
and above and enclosed sub-staon with transformaon capacity of 5 MVA and
above for use in the event of re or smoke.
RULE-44. Instrucons for restoraon of persons suering from electric shock-
(1) Instrucons for restoraon of persons suering from electric shock in English ,Hindi or
local language shall be axed by the owner.
(2) In every high voltage or extra high voltage generang staon ,substaon etc, an arcial
respirator shall be provided and kept on good working condion.
(3) The owner of every generang staon, enclosed sub-staon, enclosed
switch-staon and every factory should that all the persons employed by him are acquainted
with these instrucons and must apply.
RULE-45. Precauons to be adopted by consumers 1[owners occupiers], electrical
contractors, electrical workmen and suppliers-
(1) No electrical installaon work, including addions, alteraons, repairs and
adjustments to exisng installaons, except such replacement of low voltage domesc
appliances shall be carried out by the user. Other installaon works like addion of extra
circuit, alteraons, adjustments to the exisng installaon shall be carried out by an electrical
contractor who is licensed by state government.
RULE-46. Periodical inspecon and tesng of consumer’s installaon. -
(1) Installaons shall be periodically inspected and tested in every 5 years.
(2) Fees for such inspecon and test be determined by the central or the state
Government.
General condions relang to supply and use of energy
Rule-47 Tesng d consumer's installaon
---If a consumer needs a new or addional supply of energy, he has a to submit applicaon to
the suppler. Then the supplier shall inspect and test the consumer's installaon.
→Aer geng approval from Inspector new Supply of energy or reconnecon of the Supply
aer a period of six months is provided to the consumer.
Aer inspecon if the inspector & feels that the installaon is not safe and can be
dangerous to consumer, then the inspector will give noce fo modicaons
No Consumer shall commission his generang plant of a capacity exceeding 10KW without
wrien approval of the Inspector.
Rule-48 Precauons against leakage before Connecon
The supplier shall not provide energy Supply to the installaon ore apparatus unless he is
Sased that there is no leakage from the installaon or any apparatus.
For example insulaon resistance of medium and low voltage installaon shall be at least 1
Mega ohm.
Rule 49 Leakage on Consumer's Premises
If the supplier/inspector found that insulaon resistance is low and which is likely to cause
danger , he shall disconnue the supply of energy to the installaon and gave 48 hours,
disconnecon of supply and shall not reconnect unl the cause of leakage has been removed.
Rule 50→ Supply and use of energy
Energy shall not be supplied, trans formed, converted or wed unll the following
arrangements are not done
Arrangement must be done to completely isolate the supply to the installaon. A leaked
Switch with fure(s) are a Circuit breaker must be used for low and medium voltage Consumer.
and High voltage consumer also. Similarly a circuit breaker is used for HV( 11 KV to 3kV) and
EHV consumer. Every consumer shall ensure that no person other than the supplier shall
interfere with the service lines and apparatus placed by the supplier.
Rule 50A Addional provision for supply use of energy in mul-storied building
1 ) Before 30 days the consumer must gave applicaon for commencement of supply (new or
old ) to the inspector with all parculars. The supply of energy shall not be commenced or
recommenced within this period.
2) The supplier shall provide cut out or breaker at a posion not more than 2.75 meters
3) The owner of a mulstoried building shall ensure the safety of installaon
4) No other service popes shall be taken along with the power cable.
Rule 51. All conductors other than overhead lines Shall be completely enclosed in
mechanically strong metal casng or metallic covering
→All metal works, enclosing shall be connected with an earthing system
A clearance of 1 meter shall be provided in front of switchboard
If the installaon is done where gases/chemicals are produced, the installaons,
Equipments and apparatus must be provided ame proof, dust ght, totally enclosed
protecon.
Rule-52 Appeal to Inspector in regard to defects:-
If any applicant dissased with the acon of supplier in declining for a to commence he may
appeal to the inspector to test the installaon.
Rule-53 Cost of inspecon and rest of consumer's InstallaonThe cast of rst inspecon
and test of consumer's installaon Carried out shall be paid by the consumer
Rule-54 Voltage Regulaon.
In case of low ore medium voltage the supply Voltage shall not more than 6 percent .
In case of high voltage, voltage shall not more than 6% on higher side and 9% on lower
side.
→Fore extra high voltage→
1) higher side 10%
2) Lower side → 12.5/
Rule-55 Declared frequency of supply to Consumer
The supply frequency should shall be allowed to vary between +3%. to -3%..
Rule-56 Sealing of meters and cut outs.
A Supplies may ax one or more seals to Cut-out and to any meter, maximum demand
indicator on the consumer's premises.
→The consumer shall ensure that no such seal broken other than supplier.
Rule-57 Meters, maximum demand indicators and other apparatus on consumer's premises
Error of any meter/maximum demand indicators / other apparatus placed on consumer's
premises should not exceed 3 percent above or below the accurate value.
No meter shall register at no load.
Every supplier shall examine, test and regulate all meters, maximum demand indicators
etc. before their rst installaon
→Every supplier shall maintain a register of meters showing the date of last test, last error,
limit of accuracy aer adjustment.
Rule 58 -The point of commencement of supply
The point of commencement of supply of energy to a consumer shall be considered to be the
point at which incoming terminal of the wet-outs installed by the consumer.
Rule 59-Precauons against failure of supply
The layout of elecon supply lines in an area shall be seconalized and provided with cut-outs
or circuit breakers . So the fault occurring in any part of a circuit can not transmits to other.
ELECTRIC SUPPLY LINES, SYSTEMS AND APPARATUR FOR LOW AND NEDIUM VOLTAGE
Rule-60-Test for resistance of insulaon
If any closer supply line of low or medium voltage has been disconnected from a System or
addion of new circuit or repair is done by disconnecng the supply , such electric Supply line
shall not be reconnected to the system unl the following test is done as per rule 48.
(leakage or insulaon resistance)
Rule 61- Connecon with Earth.
Neutral conductor of a 3-phase 4 wire system and middle conductor of a 2 phase 3- wire
system shall be earthed.
If a system consist of concentric Cables, the external conductor must be earthed
→The frame of every generator, motor, mate metallic part of all transformer shall be earthed.
→All earthing syst Systems shall be test earth resistance on dry days tesng fore
Rule-62 System at medium Voltage:- Where a medium voltage supply system is employed,
the voltage between Earth and any conductor forming part of the same system shall not i
under normal condions, exceed low voltage
Rule-63. Approved by Inspector. →If an installaon has been disconnected for one year , to
recommence the supply the supplier and owner must ensure that the supply lines and
apparatus are placed in posion, properly tested and examined. Then applicaon is given to
the inspector for inspecon.
The owner of any high or extra high voltage installaon can not make addional
installaon or altercaon to the system unl he has the wrien approval from inspector.
Rule- 64. Use of energy at high and extra high voltage
All conductors and apparatus situated on Consumer premises should be at inaccessible
posion, all operaon related to the all items should be done by authorized sard person only.
→The consumer must place the apparatus and meter of the supplier in a separate building for
all me assess of the supplier.
All pole type sub-staons are constructed and maintained in accordance with BIS.
Rule 65-Tesng, operaon & Maintenance.
→New HV OR EHV, apparatus, supply line, cables shall be commissioned aer site test as pert
BIS
If HV or EMV apparatus , supply line or cables has disconnected fore 6 months are more
fore recommission of the items tesng. must be done as per BIS
All apparatus, supply line ore cables shall be maintained en "healthy condions and
periodical tests should be carried out.
Records of all tests, maintenance work and repairs of apparatus, Supply line and Cables
shall be duly kept.
Rule-66- Metal sheathed electric supply line, Precauon against excess leakage.
The metal sheathing of conductor must be electrically connuous and connected with
earth.
the resistance of earth connected with metallic sheath shall be kept low.
→If electric-Supply line has concentric Cable the outer conductor may shall be Connected
with earth.
Rule 67- Connecon to earth
All non-current carrying metal parts, associated with HV/EHV installaon shall be eecvely
earthed to a ground System or Mat.
Rule-68 General condions for transformaon and control of energy.
Sub-staons and switching staons shall be preferably elected above the ground. If it is
required to build an underground substaon , proper Venlaon system proper must be
provided.
Rule-70- Condensers
Suitable provision shall be made for immediate and automac discharge of every Stac
condenser on disconnecon of supply.
OVERHEAD LINES
Rule-74. Material and strength
→All conductors of over head lines shall have breaking strength of not less than 150kg if
voltage is low and the span is less than 15m.
If the span is more than 15m and voltage is low, medium or high than breaking strength of
the overhead lines should not be less than 350kg.
Rule-75
Joints between conductors of overhead lines shall be mechanically and electrically secure
under the condions of operaon.
Ulmate strength of the joint shall not be less than 95 percent of the original conductor
and electrical conducvity shall not be less than that of original conductor
Rule-76.
Factor of Safety= Breaking strength/ Working strength or stress
* For metal supports = 1.5
* For mechanically processed concrete Supports = 2:0
* For hand-molded concrete supports = 2-5
* Wood supports = 3.0
*Stay wire, guard wire. = 2.5
Rule-77. Clearance above ground of the lowest conductor
If the supply line is across any street:-
*Low and Medium Voltage = 5.8m
*For high voltage line = 6.1m
If the supply line is along with any street:-
*Low and Medium Voltage = 5.5m
*For high voltage line = 5.8m
If the supply line is away from any street or populaon:-
*Low and Medium Voltage = 4.6m
*For high voltage line = 4m
For high voltage line above 11kv = 5.2m
Rule-78- Clearance between conductors and trolley wires
*Low and medium voltage lines →1.2m
*High voltage line upto 11 kv →1.8m
*High voltage live above 11KV→2.5m
* Extra-high voltage line→3.0m
Rule 79-clearcances from building of low and medium voltage lines and service lines.
Low and medium voltage→
a) Vercal clearance from a building. = 2.5m
b) Horizontal clearance from a building = 1.2m
Rule-80-Clearance between building and high cand extra high voltage line
a) Vercal clearance -
*Voltage upto 33KV →= 3.7m
*For E-H-V line→3.7m+0.3m (for addional 11KV)
b) Horizontal clearance.
*upto 11KV →1.2m
*11KV to 33KV 2m
* EHV lives. →2m+ 0-3 (for addional 33 KV)
Rule 86. Condions to apply where telecommunicaon lines and power lines are
carried on same supports-
(1) Every overhead telecommunicaon line erected on supports carrying a
power line shall consist of conductors each having a breaking strength of not less
than 270 kg.
(2) Every telephone used on a telecommunicaon line erected on supports
carrying a power line shall be suitably guarded against lightning and shall be
protected by cutouts.
(3) Where a telecommunicaon line is erected on supports carrying a high or
extra-high voltage power line arrangement shall be made to safeguard any
person using the telephone against injury resulng from contact, leakage or
inducon between such power and telecommunicaon lines.
Where an overhead line crosses another overhead line, clearances shall be as
Rule 87. Lines crossing or approaching each other-
Where an overhead line crosses another overhead line, clearances shall be as
under: -
Sl.
No.
Nominal System
Voltage
11-66
KV
110-132
KV
400 KV
800 KV
1.
2.
3.
4.
5.
6.
Low & Medium
11-66 KV
110-132 KV
220 KV
400 KV
800 KV
2.44
2.44
3.05
4.58
5.49
7.94
3.05
3.05
3.05
4.58
5.49
7.94
5.49
5.49
5.49
5.49
5.49
7.94
7.94
7.94
7.94
7.94
7.94
7.94
Rule 88. Guarding-
*Every guard-wire shall be connected with earth at each point at which its
electrical connuity is broken.
*Every guard-wire shall have an actual breaking strength of not less than
635 kg and if made of iron or steel, shall be galvanized.
*Where there is only one trolley-wire, two guard-wires shall be erected as
in diagram A.
Rule 89. Service-lines from Overhead lines- No Service-line or tapping shall be
taken o an overhead line except at a point of support.
Rule 90. Earthing-
(1) All metal supports and all reinforced and prestressed cement concrete
supports of overhead lines and metallic ngs aached thereto, shall be
permanently and eciently earthed. For this purpose a connuous earth wire
shall be provided and securely fastened to each pole and connected with earth
ordinarily at three points in every km., the spacing between the points being as
nearly equidistance as possible. Alternavely, each support and the metallic
ng aached thereto shall be eciently earthed.
(2) Each stay-wire shall be similarly earthed unless insulator has been placed
in it at a height not less than 3.0 m from the ground.
Rule 91. Safety and protecve devices-
(1) Every overhead line, (not being suspended from a dead bearer wire and
not being covered with insulang material and not being a trolley-wire) erected
over any part of street or other public place or in any factory or mine or on any
consumerspremises shall be protected with a device approved by the Inspector
for rendering the line electrically harmless in case it breaks.
(2) An Inspector may by noce in wring require the owner of any such
overhead line wherever it may be erected to protect it in the manner specied in
sub-rule(l).
ELECTRICAL INSTALLATIONS
2. 1 Electrical installaons, domescs, industrial, Wiring System, Internal distribuon of
Electrical Energy. Methods of wiring, systems of wiring, wire and cable, conductor materials
used in cables, insulang materials mechanical protecon. Types of cables used in internal
wiring, mul-stranded cables, voltage grinding of cables, general specicaons of cables.
2. 2 ACCESSORIES: Main switch and distribuon boards, conduits, conduit accessories and
ngs, lighng accessories and ngs, fuses, important denions, determinaon of size of
fuse – wire, fuse units. Earthing conductor, earthing, IS specicaons regarding earthing of
electrical installaons, points to be earthed. Determinaon of size of earth wire and earth
plate for domesc and industrial installaons. Material required for GI pipe earthing.
2. 3 LIGHTING SCHEME: Aspects of good lighng services. Types of lighng schemes, design of
lighng schemes, factory lighng, public lighng installaons, street lighng, general rules for
wiring, determinaon of number of points (light, fan, socket, outlets), determinaon of total
load, determinaon of Number of sub-circuits.
ELECTRICAL INSTALLATION
WIRE:- single core strand may be bare or cover with insulaons known as wire.
CABLE:-Several wire stranded together is known as cable. (Cover with insulaon)
NECESSITY IN A CONDUCTOR/WIRE/CORE:
Good conductor of electricity (low resisvity)
Cheaper in cost.
Safety (not provide leakage current )
Easily available.
High mechanical strength, durable.
Melng point should be high.
High resisvity to corrosion, oxidaon, withstand dampness.
High resisvity towards chemical reacon.
PARTS OF CABLE:
Cable consists of three parts
a) Conductor/Wire/Core
b) Insulaon/Dielectric
c) Cable jacket
-
a) Conductor/core:-It carries current.
b) Insulaon/Dielectric:-covering part is used to avoid leakage current from the conductor.
c) Cable jacket;-The protecve covering for protecon of insulaon from mechanical
damage.
CONDUCTOR MATERIAL USED IN CABLES:-
1. COPPER
2. ALUMINIUM
3. SILVER
4. GOLD
5. LEAD & TIN
6. STEEL
7. GALVANISED STEEL
1.COPPER:-
It has high conducvity.
Less resisvity, durable and ducle.
Mechanically strong, hard
High resisvity to corrosion, oxidaon, high temperature.
Welded easily, soldered.
Cheaper in cost.
2.ALUMINIUM
Cheaper in cost
Long distance power distribuon ( use in place of copper for bare electric cable)
Aluminium
copper
1. Less
conducvity than
copper (60% of
copper).
2. required
Aluminium is
1.61mes that of
copper in volume.
1. More conducvity
than cthththaththancoppercccccccaluminium.
aluminium.
INSULATING MATERIALS:- It is used to prevent the leakage current from conductor.
Properes of insulang material:-
High resisvity.
High exibility.
High dielectric strength.
Non-inammable (not catching re easily/not inammable).
Non-hygroscopic ( it does not absorb water and moisture from atmosphere).
High resisve to moisture, acid, or alkalis.
Capabilies to withstand high rupturing voltage and high temperature.
Capability withstand wind, force, Iceland.
TYPES OF INSULATING MATERIALS:-
1.RUBBER
Advantages:-
It has good dielectric strength(30KV/MM)
It has high insulang properes.
High relave permivity.
Disadvantages:-
It absorbed moisture.
Oen when heated to a temperature of 60 to 70
Ages when expose to light.
Deform when warm and brile when cold.
It is scky in nature.
So, hat pure rubber is not used for insulaon.
2. VIR (VULCANISED INDIAN RUBBER)
Advantages:-
It has great mechanical strength.
It has good dielectric strength (60KV/MM)
It has good insulang properes.
It does not absorb moisture from atmosphere.
It is Durable
VULCANISATION
It is a chemical process for converng natural rubber to more durable material by
adding of sulphur.
Sulphur reacts with copper and corroded the copper surface. So this can be avoided
by providing a nned layers over the copper surface.
It may be used in internal wiring and other low voltage insulaon. (decoraon)
3. SILK& COTTON:-
This is used in low voltage cable.
Conductors may have a single layer or double layer covering depending upon the
requirements of service.
Silk of coon covered wires are usually used for instruments and motor windings
4. IMPREGNATED PAPER
Advantages:-
It has high dielectric strength. ( 30 kv/ mm)
It has good insulaon resistance.
It has low cost.
Disadvantages:-
It absorbed moisture (hygroscopic in nature).So that it always provided with
some protecve covering and never le unshield.
To make it noninammable paper, impregnated with some compound like
paran, napthenic and resin.
5. POLYVINYLE CHLORIDE (PVC)
It has good dielectric strength.
It has good insulang properes.
Good mechanical strength.
It does not absorb moisture.
It does not reacts with acid & alkali (used in house wiring ,cable factories)
It is used for low & medium voltage domesc & industrial light and power installaon.
It is low cost.
MECHANICAL PROTECTION
Insulang materials are mechanically weak so protecon against mechanical injury is
required.
Protecon is provided by steel, aluminium on PVC covering.
Protecon against damage & moisture.
TYPES OF CABLES USED IN INTERNAL WIRING
The wire employed for internal wiring of building may be divided into dierent groups
according to:-
1. Conductors used (according to the conductors material used in cable:-
a) Copper conductor
b) Aluminium conductor
2. According to the numbers of core in cables:-
a) Single core cable c) Three core cable
b) Twin core cable d) Four core cable
3. According to voltage grading, the cables are 2 types:-
a) 250/500 volt cable
b) 660/1100 volt cable
4. According to types of insulaon the cables are:-
a) VIR insulated cables
b) TRS/CTS cables TRS-Tough rubber sheath
c) Lead sheath cable CTS-Cab tyre sheath
d) PVC Cable
e) Waterproof cable/weather proof
f) Flexible cord & cables
1. VIR INSULATED CABLE
The cables are available in 250/500 volt and 660/1100 volt.
It consists of n & copper conductor covered with a layer of VIR Insulaon.
Over the rubber insulaon coon tap sheath covering with moisture resistance
compound bitumen wax to make the cable moisture proof.
Conductor reacts with VIR insulaon therefore to prevent the reacon a n layer is
given in the conductor.
VIR is used to protect the conductor from mechanical injury.
Bitumen & coon tap are used to protect the insulaon from weather & moisture.
2. TRS/CTS CABLE
These cables are available in 250/500 volt and 660/1100.
TRS/CTS cable is vulcanized rubber, insulated conductor with an outer protecve
covering of tough rubber which provides addional insulaon and protecon against
wear & tear.
These cables are water proof and hence can be used in wet condion.
This cable is available in single core, twin core, three cores etc.
The cores are insulated from each other and covered with a common sheathing.
3. LEAD SHEATH CABLE
This cable is available in 250/500 volt.
It consists of vulcanized rubber insulated conductors cover with a sheath of lead.
The lead sheath provides a very good protecon against the moisture and mechanical
injury. So this can be used without casing or conduit system.
This cable is available in single core, twin core, three cores etc.
4. POLYVINYL CABLE (PVC)
These cables are available in 250/500 volt & 660/1100 volt grade.
It is used incasing-capping, baen& conduit wiring system.
Since PVC is harder than rubber it does not require coon tapping over it for
mechanical and moisture protecon.
These type cable conductors are insulated with PVC insulaon.
ADVANTAGES
Beer insulang properes.
Low cost
Beer exibilies.
No chemical eect on metal of the wire.
5. WEATHER PROOF CABLE
These cables are available in 250/600 volt and 660/1100 volt grade.
These cables are either PVC or VIR insulated conductors and then compounded with
weather resisng material.
These cables are not aected by heat, sunlight, rain.
It is used for outdoor wiring, power supply or industrial supply.
6. FLEXIBLE CORD & CABLE
It consist of wire silk, coon, plasc covering.
Flexible cord have n-copper conductor.
Flexibilies and strength is obtained by using conductors having large no. of strand.
This wire or cable are used as connecng wires for such purpose as from ceiling rose to
lamp holder ,socket outlet to portable apparatus such as fan ,lamp, heater ,etc.
MULTISTRAND CABLE
Advantages of mul strand cables w.r.t single solid conductors.
Mul strand cables are more exible and durable and therefore can be handle
conveniently.
The surface area of mul strand cable is more as compare to the surface area of
equivalent single solid conductor .so heat radiang capacity is more in mul strand
cable because of its large area.
Skin eect is beer as conductors are tubular, specially in case of high frequency.
The no. of strand is stranded cable must be 3,7, 19, 37, 61, 91 etc.
VOLTAGE GRADING OF CABLES:-
This species the safe voltage which the insulaon of the cable can withstand.
The cables employed for domesc wiring are graded as 250/500 volt & 660/1100 volt
grade.
GENERAL SPECIFICATION OF CABLES:-
1. SIZE OF CABLE:
19/24
19-No. of strand in cable 24-diameter of each strand in mm
2. Types of conductors used in cable ( co & Al )
3. The no.of core that cable consists of ( single core, twin core ,three core ,four core)
4. Voltage grading (250/500 volt & 660/1100 volt grade)
5. Types of cable with clear descripon regarding insulaon, shielding etc.( PVC etc.)
LIGHTING ACCESSORIES AND FITTINGS
1. SWITCH
2. CEILING ROSE
3. SOCKET OUTLET
4. PLUGS
5. LAMP HOLDER
1. SWITCHES
A switch is used in an electric circuit as a device for making or breaking the electric ckt
in a convenient i.eis by the simple moon of handle or knob to connect together or
disconnect two terminal to switch cables or wires are connected.
2. TYPES OF SWITCH:-
a) ACCORDING TO THE TYPE OF BASE MATERIAL:-
Porcelain switch( high rang)
Bakelite switch( low rang)
b) ACCORDING TO THE COLOUR
black
white
Brown
c) ACCORDING TO OPERATION
One way switch
2 way switch
2 way centre o switch
Double pole main switch
Single pole single throw
Single pole double throw
Double pole double throw
Double pole main switch
Single pole main switch
1. ONE WAY SWITCH
6 amp,250 volt --------light load ( fan, tube light)
16 amp,250 volt -------heavy load(washing machine, heater, AC etc)
2. TWO WAY SWITCH
The switch of this type consist of 3 or 4 terminals
The switch of this type is usually used for staircase wiring or circuit where one point is
to be controlled from two dierent places.
6 amp, 250volt -------(light load)
Connecon diagram of 2 way switch
3. 2 WAY CENTRE OFF SWITCH
6 amp ,250 volt
4. SINGLE POLE MAIN SWITCH
5. DOUBLE POLE MAIN SWITCH
6. SINGLE POLE SINGLE THROW
7.SINGLE POLE DOUBLE THROW
8.DOUBLE POLE DOUBLE THROW
CEILING ROSE
The ceiling rose is used to connect the pendent lamp, fan and uorescent tube to install
through exible wire.
It consists of 2 parts
1. Base 2.cover
It is made of bakelite, porcelain
TYPES OF CEILING ROSES
1. 2-way ceiling rose:-
It is ed with two terminal plate.
2. 3-way ceiling rose:-
It is ed with 3 terminal plates. Rang 6A, 250 volt
SOCKET OUTLET:-
The socket outlet are used to supply outlet connecon when ever required for electrical
appliances such as TV, iron table fan.
TYPES OF SOCKETS
1 PIN SOCKETS
3 PINSOCKETS
5 PIN SOCKETS
LAMP HOLDER:-
It is used to support the lamp and also to connect of electricity.
These are design for quick removal, replacement. Of the lamp.
It is made of Bakelite with porcelain interiar.
TYPES OF LAMP HOLDER:-
1. Pandent holder
2. Angle holder
3. Slanng holder
PLUG:- Plugs are use to connect the supply from the socket outlet for electrical appliances
such as TV,
Iron
2pin plug 3pin plug
PARALLEL OPERATION ADVANTAGES
The supply voltage is uniform in each load.
In case the light or same other equivalent goes out of order, it will not aect the supply
of current to other light etc as each one of them is individually connected to line.
The voltage in the ckt will be uniform and every will glow with full brightness.
SERIES CONNECTION
The ckt useful for decorave lighng for marriage and other places where
groups of lamps are to be control by switch instead of placing separate switch
for each light.
The major disadvantages are of one light goes out of order , light and other
equipments in that ckt will go o . As the ow of current from one point to
other is stop.
SERIES PARALLEL CONNECTION
(a) With 2-way centre o switch
(b) With 2-way and o switch and one way switch
Series parallel circuit are used either to provide dim light or full bright light through the
same lamp by using special switch such as two way centre o switch .
To operate either both lamp in series or parallel by wiring two pole double throw switch
(c) CIRCUIT FOR ONLY ONE PARTICULAR LAMP BRIGHT OR TWO LAMPS IN SERIES WITH
TWO WAY AND SINGLE WAY SWITCHES
(d) TO OPERATE EITHER BOTH LAMPS IN SERIES OR BOTH IN PARALLEL BY USING 2 POLE
DOUBLE THROW SWITCH
For posion 1-2=The lamp will provide dim lights
For posion 3-4=The lamps are connected in parallel across 230 volt giving full bright light.
FUSE
It is a simple and cheapest device used for interrupng and electrical circuit under short
circuit or over load condion.
The acon of a fuse is based upon the heang eect of the electric current.
ADVANTAGES
It is cheaper form of protecon available.
It needs no maintenance.
Its operaon is completely automac.
It interrupt huge short circuit current without noise, gas, smoke.
DISADVANTAGE
Considerable me is lost in running or replacing a fuse aer operaon.
FUNCTION OF WIRE
To carry the current working current ow without heang.
To break the circuit when the current exceed the liming current.
FUSE ELEMENT MATERIAL
The material used fuse elements must be of low rang point ,high conducvity , low
cost and from deterioraon.
The material commonly use for fuse elements are n, lead ,copper, zinc, aluminium and
alloy of lead and n(60+40)
Fuse element is a low melng point material such as n, lead and zinc.
The alloy of lead and n is used for small current for fuse ( up to 15 amp)
Beyond 15 amp rang circuit copper wire fuse are used.
Either copper or lead n alloy is mostly used as an
ordinary use wire.
TYPES OF FUSE:-
(a) Supply main fuse:-
This fuse is provided by the supplier and is xed just before the service meter .The
rang of supply main fuse will be as from bad current of the consumers.
(b) Consumers main fuse:-
This is another fuse of rang slightly less than that of supply main fuse and placed aer
the consumers main switch.
(c) SUB Circuit fuse:-
The total wiring system is divided in to no. of sub circuit or branch. A separate fuse is
provided for each branch circuit and is known as sub. Circuit or branch circuit use
Metals
Melng
point
silver
980
n
240
zinc
419
lead
328
copper
1090
aluminium
665
(d) POINT FUSE :-
In good quality indoor wiring in building light and plug point is provided with its
individual fuse known as point fuse.
IMPORTANT DEFINATION ( 2 MARK)
FUSE:-
Fuse is a current interrupng device which break or open the circuit by fusing the elements
when the current in the ckt exceed a certain voltage.
FUSE ELEMENTS OR FUSE WIRE:-
It is that point of the fuse which actually melt when an excessive current ow in the circuit
and thus isolate the faulty device from the supply.
CURRENT RATING:-
It is dene as the RMS value of current which the fuse wire can carry connuously without
deterioraon and with temperature rise with in specic limit.
FUSING CURRENT:-
It is dene as the minimum value of current at which the fused elements or fuse wire melt. Its
value will be more than current rang of the fuse element for a round wire the appropriate
value of fusing is given by
I=
Where k= fuse constant, depend upon the metal of the fuse elements
d =diameter of the wire
The fusing current depends upon various factor such as
1. Types of metal used.
2. The cross seconal area i.e whether round or regular secon
3. Diameter of the wire
4. Types enclose employed
5. Type of surface ( stranded)
The fusing current for stranded fuse will be less than the product of the fusing current one
strand and the no. of strand.
FUSING FACTORS:-
It is the rao between minimum fusing current to the current rang of fusing elements is
known as fusing factor and it is always greater than unity.
Fusing factor=


NO. OF
WIRE
1
2
3
4
7
FUSING
CURRENT
1
1.667
1.25
2.75
4
DETERMINATION OF SIZE OF FUSE WIRE
1. Factors responsible for deteriorang the size of the fuse wire in an installaon are:-
Maximum current rang of the circuit.
Current rang of the smallest cable in the circuit protect by the fuse.
EARTHING CONDUCTOR:-
Earthing conductor is of v high conducvity material specially we i. E copper & G.I wire.
I should be protect against mechanical injuries in corrosion.
WHAT IS EARTHING:-
Connecon of non-current carrying part of electrical apparatus such as metallic frame,
metallic covering of cables, earth terminals of sockets outlet, stay wire etc to the general mass
of earth in such a manner that at all me an immediate discharge of electric energy taken
place without danger.
EARTHING IS PROVIDED
To avoid electric shock to the human beings
To avoid risk of re due to earth leakage current through unwanted path.
IS SPECIFICATION REGARDING EARTHHING OF ELETRIC INSTALLATION:-
1. Distance of earth from Building
An earth electrode shall not be situated within a distance of1.5m from the building
whose installaon is being earthed.
2. Size of earthed connuity conductor
The conductor which is used to connect the metal body of an equipments or
appliances to the earth is known as earth connuity conductors (ECC).
It should not be less than 2.9mm
2
or half of installaon conductor size.
3. Resistance of earth
The earth resistance should be low enough to cause ow of current.
The value of earth resistance does not remain constant but change with the
weather as it depends upon the moisture contents of the soil and is maximum
during dry season.
Large power staon =0.5
Major power staon=1
Small sub-staon=2Ω
In other all cases=5Ωmaximum
4. The earth wire and earth electrode shall be of same material.
5. The earth wire shall be taken through G.I pipe of 13 mm diameter for atleast30 cm
length below ground surface to the earth electrode to protect it against mechanical
damage.
6. The earth electrode shall always be placed in vercal posion inside the earth or pit so
that it may be in contact with all the dierent earth layer.
7. All the earth wire run along the various sub circuit shall be terminated and looped
rmly at the main board and from main board, the main earth shall be taken to the
electrode.
POINT TO BE EARTH
Earth pin of 3- pin& 5- pin socket should be permanently and eciently earth.
All metallic covering containing or protecng any electric supply line or apparatus such
as iron clad switches ,iron clad distribuon fuse board, G.I pipes and conduit enclosing
VIR or PVC cable etc should be connected to earth.
The frame of energy generator, staonary motor ,portable motor and the metallic part
of all transformer and any other apparatus used for regulang and controlling energy
and all medium voltage energy consuming apparatus should be a earth by two
separate dierent connecon with earth.
Fabricang steel, transformer line tower, tubular steel or rail poles carrying overhead
conductor should be earthed.
Stay wire provide for overhead lines should be connected to earth buy connecng at
least one strand of the earth wire .
The neutral conductor of a 3phase, 4 wire system and the middle conductor of a 2pjase
,3 wire system should be earthed by two separate and dierent connecon in earth at
the generang staon and at the substaon
DETRMINATION OF SIZE OF EARTH WIRE AND EARTH PLATE FOR DOMESTIC OF MOTOR
INSTALLATION
THE LIST OF MATERIALS WITH COMPLETE SPECIFICATION FOR G.I PIPE EARTHING IS GIVEN
BELOW
MAIN SWITCH AND DISTRIBUTION BOARD
Main switch is provided immediately aer the meter board. The link main switch and
fuse unit may be provided as one unit or as separate unit.
Switch, fuse is a combined unit and is known as iron clad switch, being made of iron.
I. DPIC- Double pole iron clad switch(1 phase,2 wires)
II. TPIC-Triple pole iron clad switch (3phase,3 wires)
III. TPNIC-Triple pole with neutral link iron clad switch (3phase ,4 wires)
Since no fuse is to be provided in neutral in DPIC switch fuses,where provision is made
for fuses in both the wires , one fuse carrier is furnished with fuse elements and the
other a thick copper wire.
SWITCH FUSE REQUIREMENT GENERAL
The switches & fuse shall be enclosed in a strong metallic enclosure.
It should be dust free and weather proof and have a mounng arrangements on the
wall.
The metallic enclosure will have an earthing terminal.
The ON & OFF shall be clearly marked on it .
The xed contact and other metal parts shall be nickel plates or n where it is desirable.
DISTRIBUTION BOARD
Distribuon board is an assembly of parts, including one or more fuse or circuit breaker,
arranged for the distribuon of electrical energy to various circuit or other distribuon
board known as sub-main distribuon board.
The boards are usually metal cased, in sheet steel where earthing terminals and locking
arrangements are provided.
The number of ways depends upon the circuit or sub-circuit to be fed.
Separate distribuon fuse boxes should be provided for light and power circuit.
CONDUITS
General conduits can be classied as :-
1. Light gauge steel-plain conduit
2. Heavy gauge steel-screw conduit
3. Flexible conduit
4. PVC conduit
1.Light gauge steel-plain conduit
The external diameter of 12 mm, 16mm, 19mm, 25mm, 31mm, 38mm & 50 mm are
available.
This type of conduit is used on the surface usually in connecon with special grip ng.
It is a cheapest and quickest of the conduit installaon.
It should be used where the locaon is dry and there is lile livelihood of mechanical
damage.
2.heavy gauge steel-screw conduit
It is expensive, this type of conduit provides a permanents installaon with a maximum
protecon for the cable.
The joints into ngs are by means of screw threaded which provide mechanical
strength and good electrical connuity.
They are available in approximate 3 m. length and are threaded at the two ends.
3.Flexible steel conduit
This usually consists of light gauge galvanized steel, spirally wound and to some extent,
inter-lock so as to form a tube
The size from 19mm to 50 mm are present .
Since conduits are exible and has easily bend no elbow is required.
It is costlier than the rigid conduit.
One of the most common uses of exible metal conduit is for protecng the nal
connecon to motor.
4.PVC conduits
It is used for internal wiring because it is light in weight, shock-proof, self xing and re
resistance, acid , alkali and corrosion resistance having high insulaon value and
dielectric strength.
Such conduits can be used for both surface and concealed type wiring. Here a separate
earth wire must be run inside the tube.
CONDUITS ACCESSORIES& FITTINGS
1. CONDUIT COUPLER
It is used to joint two length of conduit. The length of screw conduits are always
threated at both end on outer side.
2. GRIP COUPLER
In grip coupler, no extra labour is required for making threads. The ends of conduits are
placed in the grip coupler and screw it ghtly.
It is covered above two conductor and the screw is used to make it ght.
3. FLEXIBLE CONDUIT COUPLER
For coupling a exible conduit to the rigid conduit a combine coupling is used.
4. BENDS ,ELBOW, & TEES
BEND:- Bends are usually used for change in direcon of conduit.
ELBOW:
Elbows are of shorter radius, are only used where sudden right turn is required.
TEES
CONDUIT BUSHINGS
This are used when the rigid conduit enter the conduit box or a hole which is not threaded.
This are used to prevent cable from being cut by the edges.
It is up two types.
a) Male -outer threads
b) Female-inner threads
CONDUIT REDUCER
Conduit reducers are used when the size of conduit change.
Conduit reducer have both male & female threads.
FIXING OF CONDUIT
It is used to x the conduit over the wall.
CLIP:- Clip are used for xing the conduit on rough brick walls and in concealed wiring.
SADDLE:
Saddle are used for xing the conduit where clips cannot provide a rm enough hold or a
single screw cannot be dependent upon for xing.
LOCKNUTS/CHECK NUTS:
This are used when rigid conduit enter a conduit box.
CONDUIT NIPPLES
This serve the same purpose as conduit bushing.
This are rarely used due to their higher cost.
CONDUIT BOXES
The conduit boxes are used in surface conduit wiring as well as concealed conduit wiring. It
serve the following purpose.
It is used to provide connecon to rigid fan and other point.
for pulling of cable into the conduit. Boxes serving this purpose are known as inspecon box .
this are provided aer every 30 cm length straight run.
For housing juncon of cables, the conduit boxes serving this purpose are known as juncon
box.
WIRING SYSTEM
A network of wires connecng various accessories for distribuon of electrical energy from
the supply meter board to the numerous electrical energy consuming device such as lamps &
fan and other domesc appliances through controlling & safety device is known as wiring
system.
TYPICAL HOUSE WIRING SYSTEM
SYSTEM OF DISTRIBUTION OF ELCTRICAL ENERGY
As per recommendaon of Indian standard, the maximum number of points of light, fan and
5A sockets outlet that can be connected in one circuit is 10and the maximum load that can be
connected in such circuit is 800 wa, in case more load or points are required to be connected
to the supply, then it is to be done by having more than one circuit.
The system of distribuon of electrical energy is two types
a) Distribuon board system
b) Tee system
a) DISTRIBUTION BOARD SYSTEM
TREE SYSTEM
METHODS OF WIRING
There are two methods of wirings known as joints box system (tee system ) and loop in system
wiring.
JOINTS BOX/ TEE SYSTEM
INTERNAL WIRING
3 . 1 Type of internal wiring, cleat wiring, CTS wiring, wooden casing capping, metal sheathed
wiring, conduit wiring, their advantage and disadvantages comparison and applicaons.
3 . 2 Prepare one esmate of materials required for CTS wiring for small domesc installaon
of one room and one verandah within 25 m2 with given light, fan & plug points.
3 . 3 Prepare one esmate of materials required for conduit wiring for small domesc
installaon of one room and one verandha within 25 m2 with given light, fan & plug points.
3 . 4 Prepare one esmate of materials required for concealed wiring for domesc installaon
of two rooms and one latrine, bath, kitchen & verandah within 80m2 with given light, fan &
plug points.
3 . 5 Prepare one esmate of materials required for erecon of conduct wiring to a small
workshop installaon about 30m2 and load within 10 KW.
CHAPTER-3 INTERNAL WIRING
TYPES OFINTERBNAL WIRING
Following are the type of internal wiring usually employed in industries and house
wiring;-
1. Cleat wiring
2. Wooden casing & capping wiring
3. C.T.S/T.R.S or baen wiring
4. Lead sheathed or metal sheathed wiring
5. Conduit wiring
1. CLEAT WIRIG
In this type of internal wiring the cable used are either VIR or PVC.
The cables are held by porcelain, cleat above wall or ceiling.
The cleats are made in two halves one is base and other is cap.
The base is groove to accommodate the cable and the cap is put over it and a whole of
it then screwed on wooden plug (gus) over the wall or ceiling.
The cleat are up three types
One groove-one cable
Two groove-two cable
Three groove-three cable
The cleat should be usually used at interval of 30 cm and in no case at more than 60 cm.
ADVANTAGES
It is cheapest system of internal wiring.
It’s installaon and dismantlement is easy and quick.
Inspecon, alternaon and addion can be easily made.
Skill required is lile.
DISADVANTAGES
It is not good looking.
It is quite temporary & destroy quickly.
The insulaon dampness from the atmosphere hence this system of wiring can be used
in damp place.
Oil& smoke are injurious to VIR insulaon.
FIELD APPLICATION
The wiring of this type is very suitable for temporary installaon in dry places, where
appearance is not so important and cost is the main consideraon.
2. WOODEN CASING & CAPING WIRING
This is one of the earliest systems of wiring.
The cables used in this type of wirings are either VIR or PVC.
It has two halves, one is casing and another is capping.
The casing consist of V – shaped grooves and is covered at the top buy means of
rectangular strip of wood known as capping.
The varnished is used to protect wood from white ants.
ADVANTAGES
Cheaper in cost as compare to lead sheath wiring.
Easy to install and rewire.
It provides good insulaon as conductors are at a good distance apart.
Easy to inspect by opening the capping.
DISADVANTAGES
This type of wiring is also coated with pain to varnish to protect from dampness. So it
can be used in damp place.
Since there is a risk of re. It cannot be used where there is a possibility of re hazard.
This type of wiring can be used only on surface and can be concealed in plaster.
Since it require beer work skills, the labour cost is higher.
FIELD APPLICATION
This type of wiring is suitable for low voltage domesc installaon in dry places and
where there is no risk of re.
PVC CASING & CAPING WIRING
Due to increased cost of teak wood, the wooden casing & capping are becoming
absolute and PVC casing &capping are being used.
This type of wiring is achieved by using hollow channel made of PVC plasc.
3. C.T.S/ T.R.S OR BATTEN WIRING
T.R.S-Tough rubber sheathed wiring
C.T.S-Cab Tyre sheathed wiring
In this type of wiring the cables used may be single core, twin core or three core T.R.S
cable with a circular shape.
T.R.S cables are suciently chemical proof, water proof, steam proof but are slightly
aected by lubricang oil.
T.R.S cables are run on perfectly straight and well varnished teak wood baen.
The width of baen depends upon number and size of cables to be carried by it.
The wood baens are screw to wood by plugs at an interval not exceeding 75 cm.
The cables are held on the wood baen by means of n-brass links clips at an interval of
10 cm or 15cm.
ADVANTAGES
Its installaon is easy and quick.
Its life is suciently long.
Within certain limits it is re proof.
It can withstand the acon of most chemical such as acids &alkalis.
It is cheaper than other types of wiring excepts cleat wiring.
If the job is carried out with a care it gives a nice appearance.
DISADVANTAGES
Good workmanships is required forth is type of wiring.
This type of wiring cannot be recommended for use in situaon open to sun & rain
FIELD APPLICATION
The T.R.S wiring is suitable for low voltage installaon in domesc & commercial
building.
It cannot be used in damp places.
4 .LEADSHEATHED / METAL SHEATHED WIRING
In this type of wiring the cables used are T.R.S or P.V.C with an outer covering of sheath
of lead aluminium alloy containing about 95% of lead.
This metal sheath protecon to the cables from mechanical injuries, dampness and
atmospheric corrosion.
The whole lead covering is made electrically connuous and is connected to earth at
the point of entry to protect against leakage current.
ADVANTAGES
It provides protecon against mechanical injuries beer than that of T.R.S wiring.
It is easy to x and look nice.
Its life is long if proper earth connuity is maintain throughout.
It can be used in damp situaon provided protecon against moisture.
It can be used in situaon exposed to rain & sun.
DISADVANTAGES
It is costlier than T.R.S wiring.
In case of damage of insulaon the metal sheath becomes alive and gives shock.
Skilled labour & proper supervision is required.
5.CONDUIT WIRING
In this system of wiring al wires are enclosed in steel pipe known as conduit ( PVC or
VIR).
There are3types of conduit wiring
1. Concealed conduit wiring.
2. Surface conduit wiring
3. Flexible conduit wiring
1. CONCEALED CONDUIT WIRING
The conduit are embedded along wall or ceiling in plaster at the me of construcon.
The conduit should be electrically& mechanically connuous and connected to earth at
suitable place through earth wire.
The conduit used for this purposes is up two types.
1. Light gauge conduit
2. Heavy gauge conduit
PVC conduit pipes are also available now and are increasing being employed in place of
steel conduit.
PVC. Conduits are cheaper in cost. It required less me to install. Such conduits are
resist to acids, alkalis, oil & moisture.
2.SURFACED CONDUIT WIRING
The conduit in surface conduit wiring is placed on the surface of the wall and hold with
the of conduit saddle.
This system of wiring is applied in the industrial wiring.
3.FLEXIBLE CONDUIT WIRING
The exible conduit pipe is a pipe which can bend or twist without the change in its
diameter.
The exible conduits are not used for general electrical wiring system. it is used for
connecng rigid conduit with machine terminal box in case of motor wiring, energy
meter and main switch in case industrial & domesc wiring system.
ADVANTAGES
It provides protecon against mechanical damage.
The whole system is water proof.
Replacement and alternaon of defecve wiring is easy.
Its life is long if the work is properly executed.
It is shock proof if earthing &bonding is properly done.
DISADVANTAGES
It is a very costly system of wiring.
Experience & highly skilled labour needed for carrying out the job.
Q.1 The plan of a single room of size 5mtsX4mts is given below .The room is required to be
provided with one lamp, one fan, uorescent tube and one 5 Amp socket –outlet. Each of
the points is controlled by its individual switch. Mark the locaon of the electrical points
suitably and draw the installaon plan. Also draw the wiring diagram. Calculate the total
length of wire and other materials and prepare complete list of materials required for wiring
the room in concealed steel conduit system of wiring .No main switch is to be provided as
the entry of the sub-circuit is from adjoining room.
Soluon
Assume
a) Total height from oor to ceiling=3.5 mts
b) Height of H.R from oor=3.0 mts
c) Height of switch board from oor=1.5mts
d) Light and tube points from ceiling=0.5 mts
Calculaon for length of conduits pipe of 20 mm diameter
from SB to HR=1.5 mts
from entry of circuit into room upto take o points=2.0+0.5=2.5mts
from HR to lamp point=0.5mt+4+0.5=5mts
from fan to tube points=2.5+0.5=3 mts
total length of conduit pipe=(1.5+2.5+5+3)mts=12mts
taking 10% for wastage=1.2 mts
total length of conduit pipe required for wiring the room=13.2 mts
Calculaon for length of phase wire
from point of entry of circuit into room upto SB= 2(HR)+1.5(VR)=3.5 mts
from SB to fan =1.5(VR)+0.5(HR)+0.5+2=4.5mts
from SB to lamp=4.5+2+0.5=7 mts
from SB to tube point=4.5+2.5+0.5=7.5 mts
total length of phase wire=(3.5+4.5+7+7.5)mts=22.5mts
taking 15% for wastage=3.37mts
total length of phase wire required for wiring the room=22.5+3.37=25.075mts
Calculaon for length of neutral wire
from point of entry of circuit into room up to SB= 2(HR)+1.5(VR)=3.5 mts
from SB to fan =1.5(VR)+0.5(HR)+0.5+2=4.5mts
from fan to lamp points=2+0.5=2.5mts
from fan to tube point=2.5+0.5=3mts
total length of neutral wire=(3.5+4.5+2.5+3)mts=13.5mts
taking 15% for wastage=2.02
total length of neutral wire required for wiring the room=13.5 +2.02=15.52mts
calculaon for length of earth wire (14 SWG)
length of earth wire=0.25 mt.
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
1
total length of conduit pipe (20 mm dia)
13.2 mts
2
total length of phase wire (1 mm
2
)
25.075m
ts
3
total length of neutral wire(0.5 mm
2
)
15.52mt
s
4
total length of earth wire( 14 SWG ,G.I)
0.25 mt.
5
Conduit pipe accessories for 20 mm dia
a. 1-way juncon box
b. 2-way juncon box
c. 3-way juncon box
d. Conduit bends
2 nos
1no.
2nos.
3nos.
6
One way switch,5 amp ,rang
4nos.
7
Socket,5 amp rang, 3 pin
1nos.
8
Ceiling rose, 2-plate,bakelite
2nos.
9
Lamp brass bracket with holder
1nos.
Q.2 A room and a verandah ,the plan of which is given below is required to be provided with
electrical wiring. Mark the locaon of energy meter, main switch and switch board and
electrical points suitably and draw the installaon plan showing supply path to each points
and wiring diagram .calculate the total length of wire required for wiring the room and
verandah in baen system of wiring. Prepare a list of materials with complete specicaon
of each item with approximate cost.
Soluon
Assume
a) Total height from oor to ceiling=3.5 mts
b) Height of H.R from oor=3.0 mts
c) Height of switch board from oor=1.5mts
d) Light and tube points from ceiling=0.5 mts
e) Locaon of energy meter and main switch board=0.5 mt. inside verandah on room wall
Calculaon of load
Lamps= 3X60 W=180W
Fan=1X60W=60W
Socket outlet 5 amp.=2X100W=200W
Fluorescent tube=1X40W=40W
Total connected load=480W
Load in ampere=480W/230V=2.1 amp
Selecon and rang of main switch
Rang of DPIC , Main switch =5 ampere ,250 volt grade
Selecon and rang of Distribuon board
There are only seven light/fan/socket points, hence no distribuon board will be used
Calculaon for length of baen
from main board to HR=1.5 mts =13mm X13mm (2 wire)
from SB
1
to HR =1.5mts=31mm X13mm (5wire)
from SB
2
to HR=1.5mts=25mm X13mm (4wire)
from HR above main board to L
1
=1.5mts=13mm X13mm (2 wire)
from L
1
to L
2
=0.5+3+0.5=4mt=13mm X13mm (2 wire)
from HR above SB
2
to fan =0.5+2=2.5 mts=25mm X13mm (4wire)
from fan to L
3
=2+0.5=2.5mt=13mm X13mm (2 wire)
from fan to tube point=2+0.5=2.5mt=13mm X13mm (2 wire)
total length of baen of size
13mm X13mm=1.5+1.5+4+2.5+2.5=12mt
25mm X13mm=1.5+2.5=4mt
31mm X13mm=1.5mt
taking 10% for wastage which is required for wiring the room
13mm X13mm=12mt +1.2=13.2 say 13mt
25mm X13mm=4mt+0.4=4.4mt say 4.5 mt
31mm X13mm=1.5mt+0.15=1.65 mt say 2mt
Calculaon for length of aluminium conductor VIR wire of size 1.5 mm
2
13mm X13mm=12mtX 2 wire=24 mts
25mm X13mm=4mt X 4 wire=16 mts
31mm X13mm=1.5mt X 5 wire=7.5 mts
total length of wire on baen=47.5mts
taking 15% for wastage=7.2mts
total length of phase wire required for wiring the room=47.5+7.2=55.7mts say 56mts
calculaon for length of earth wire (14 SWG)
from MS to SB
2
through SB
1
=1.5+1.5+1.5+0.25(thickness of wall)=4.75mts
taking 15% for wastage=0.47mt
taking 10% for wastage which is required for wiring the room=4.75+0.47=5.2 mts say 5.5 mts
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
DPIC main switch 5 amp rang,250 volt
grade with fuse and NL
1no.
1
total length of Dierent size of Baen
13mm X13mm
25mm X13mm
31mm X13mm
13mt
4.5 mt
2mt
2
total length of phase & neutral wire (1.5 mm
2
)
56mt
4
total length of earth wire( 14 SWG ,G.I)
5.5 mts
5
Conduit pipe accessories for 20 mm dia
a. 1-way juncon box
b. 2-way juncon box
c. 3-way juncon box
d. Conduit bends
2 nos
1no.
2nos.
3nos.
6
One way switch,5 amp ,rang
6nos.
7
Socket,5 amp rang, 3 pin
2nos.
8
Ceiling rose, 2-plate,bakelite
2nos.
9
Lamp brass bracket with holder
2nos.
9
Link clip,aluminium 40 mm long (10 cm
apart)
300 nos
9
Black enamel nails to x clips with baen
100 gms
9
Teak wood plugs (gus) at 0.75 mt interval
30nos.
9
Earthing thimbles 5 amp rang for xing
earth wire to main switch
2nos.
9
Earthing set complete with pipe,earth
wire,charcoal,salt,thimbles,nuts & bolts etc
1 set.
Q.3 It is proposed to install a power connecon of 3 phase 5 HP inducon motor for an
agriculture tube-well in the room of size 3MX3MX3M high. The motor is one metre away
from two nearest walls. Prepare the esmate in the following order.
a) Draw installaon plan showing locaon of MB and motor etc. Also mark path of
wiring by a thick line.
b) Single line diagram. Showing earth wires also.
c) Wiring diagram.
d) Decide the rang and specicaon of important materials and calculate of wire
,conduits,earth wire etc. and prepare a complete list of materials required for wiring
the room with complte specicaon of each item. Also calculate the approximate cost
for the power wiring.
Soluon
Assumpon
a) Total height of main board from oor =1.5 mts
b) Two earth wires enclosed in their respecve 15 mm dia. G.I pipe installed side by side
for earthing the motor.
c) The Motor with pumping set is installed 0.25 mt above oor on a suitable foundaon
Calculaon of load
Running current =


= 9.1 amp say 8 amp
Starng current=1.5 amp
Selecon and rang of MS
It is suggested that a TPIC, Main switch=32 amp,500 volt grade
Selecon and rang of wire
It is suggested that a PVC Insulated aluminium conductor, single core ,660 volts grade of size 6
mm
2
or 1/2.80 mm diameter, should be used for power wiring
Calculaon for length of heavy gauge conduits of 25 mm diameter
From TPIC to motor foundaon=1.5+0.25+1+o.25+0.25=3.25 mts
Taking 10% wastage=0.325mt
Total length of conduit required for wiring the motor =3.25+0.325=3.57 mts say 4 mts
Calculaon for length of heavy gauge conduits of 15 mm diameter
From starter to motor foundaon=(1.5+0.25+1+o.25+0.25)X2=3.25 mts X 2=6.5 mts
Taking 10% wastage=0.65mt
Total length of conduit required for wiring the motor =6.5+0.65=7.1 mts say 7.5 mts
Calculaon for length of exible conduits of 25 mm diameter
From energy meter to main board=1.0 mt
From main switch to starter=0.5 mt
From starter to conduit mouth=0.25mt
From motor foundaon to motor terminal block=0.25mt
Total length of conduit=(1.0+0.5+0.25+0.25)mt=2mt
Taking 10% wastage=0.2mt
Total length of exible conduit required for wiring the motor =2+0.2=2.2mts say 3.25 mts
Calculaon for length of phase wire of 6 mm
2
or 1/2/80 mm dia
From TPIC to motor foundaon=(rigid conduit +exible conduit)X3
=(3.25+2)mts X 3
=15.75 mts
Taking 15% wastage=2.5mt
Total length of phase wire required for wiring the motor=(15.75+2.5)mts=18.25 mt=18.5 mts
Calculaon for length of 8 SWG , G.I , earth wire
From starter to motor foundaon = length of conduit X 2 earth wires
=3.25 X 2 Wires
=6.5 mts
Taking 10% wastage=0.65mt
So total earth wire required for wiring the motor=6.5 +0.65=7.15mt say 7.5 mts
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
1
TPIC main switch 32 amp rang,500 volt
1no.
2
Total length of rigid conduit (25mm dia)
4 mt
3
Total length of exible conduit (25 mm
dia )
2.5 mt
4
Total length of rigid conduit (15mm dia)
7.5
5
Total length of phase wire( 6 mm
2
)
19 mt.
6
Earth wire (14 SWG)
8 mt
7
Saddle
1 pkt
8
Nuts & bolts
1 pkt
9
Wooden screw 20 mm long
30 nos.
10
PVC tape
1 pkt.
11
Bend
30 gms
12
Earthing thimbles 5 amp rang for xing
earth wire to main switch
2nos.
13
Earthing set complete with pipe,earth
wire,charcoal,salt,thimbles,nuts & bolts etc
1 set.
OVER HEAD INSTALLATION
4.1. Main components of overhead lines, line supports, factors Governing Height of pole,
conductor materials, determinaon of size of conductor for overhead transmission line, cross
arms, pole brackets and clamps, guys and stays, conductors conguraons, spacing and
clearances, span lengths, overhead line insulators, types of insulators, lighng arresters,
danger plates, an-climbing devices, bird guards, beads of jumpers, jumpers, tee-os,
guarding of overhead lines.
4.2. Prepare an esmate of materials required for LT distribuon line within load of 100 KW
maximum and standard spans involving calculaon of the size of conductor (from conductor
chart), current carrying capacity and voltage regulaon consideraon using ACSR.
4.3. Prepare an esmate of materials required for LT distribuon line within load of 100 KW
maximum and standard spans involving calculaon of the size of conductor (from conductor
chart), current carrying capacity and voltage regulaon consideraon using ACSR.
4.4. Prepare an esmate of materials required for HT distribuon line (11 KV) within 2 km and
load of 2000 KVA maximum and standard spans involving calculaon of the size of conductor
(from conductor chart), current carrying capacity and voltage regulaon of the size of
conductor (from conductor chart), current carrying capacity and voltage regulaon consider
acon using ACSR.
CHAPTER-4 OVERHEAD INSTALLATION
Q.1 In a city locality, an overhead distribuon line of 400 volts, 3 phase ,50 cycle/sec. is to be
erected along a straight route on steel tubular poles. The length of the line is 500 metres and
the line terminates at the ends. The span between adjacent poles is 50 mts. The street light
conductors are also supported on the same poles.Make a neat sketch of the last 2-3 poles and
esmate the quanty of material required for installing the distribuon line with full
specicaon of each items. Other details of the line are suggested as under.
ACSR conductors are phase lines, neutral and street light conductor of size 6/1  
(squirrel conductor). Earth wire 8 SWG , Galvanised iron
Soluon
Assuming that the connecon is taken for the line from an exisng sub-staon of 11/0.4 KV.
Length of line =500 metres
Average span=50 mts.
No. of tubular poles required=


+1=11 nos.
Length of squirrel ACSR conductor of size(6/1  mm)=(500 mts 5)+2% for sag
=2500+50
=2550 mts
In weight=85 kg/km=216.75 kg say 217kg
Length of 8 SWG, galvanized iron= 500+2% for sag
=510 mts
In weight =10 mts/kg=51 kg
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
1
Steel tubular poles (9 mts long)
11 nos
2
ACSR squirrel conductors of size(6/1 
mm)
2550 mts(218
kg)
3
E arth conductors 8 SWG GI
510 mts
(51kg)
4
shackle Insulators with ‘Dstraps i.e 5 on
each pole
55 nos.
5
Nuts and Bolts 15 mm dia ,200 mm long with
washers for xing ‘Dstraps with pole,one
for each straps
55 nos.
6
Nuts and Bolts 15 mm dia ,125 mm long
with washers for xing insulators with ‘D
straps
55 nos.
7
Earth wire pole clamp one on each end pole
2nos.
8
Eye bolts,15 mm dia ,200 mm long for
holding earth wire on intermediate pole
9 nos.
9
Guard wire of size 7/16 SWG ,for guarding at
approximate 15 places
45 mts
10
Reel insulator
15 nos.
11
Pole caps for steel tubular poles
11 nos.
12
Stay wire set complete i.e 2 sets on each
terminals poles
2+2=4 nos
13
Earthing sets complete for earng(one at
each terminal pole and one central pole)
3 sets
14
Street light ng complete with tube and
clamps
11nos.
15
Number plates with clamps
11nos.
16
Pole foundaon for each pole
11nos.
17
To complete the job miscellaneous items
such as cement ,sand, concrete etc
-
18
14 SWG ,galvanized steel wire as binding
wire
5kg
Q.2 A tube well owner wants 3 phase,4 wire power connecon to his 10 BHP motor from
an over head double pole structure having of 25 KVA ,11/0.4 KV . The double pole structure
is 300 metres away from tube well. Esmate the quanty of materials required for erecng
a line and for giving a service connecon to the tube well motor. Also draw neat sketch of
the same.
Soluon
Total connected load =10BHP
Running current=


= 14.07 amp
Starng current=1.5   amp
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building =(50%
)+21.10=31.65 amp
It is therefore suggested that
L.T core ,aluminium conductor weather proof cable of size =6 mm
2
(from
distribuon transformer to pole and from last pole to the meter box)
A.A.C of minimum size =3/3.00 mm mans stranded conductor (from rst pole to last
pole)
Average span=50 mts.
No. of Concrete pole required(9 mt. long) =


=6 nos.
Length of mans AAC conductor of size(3/3.00 mm)=(300 mts 4)+2% for sag
=1200+24
=1224 mts
In weight=58 kg/km=70.998kg say 71 kg
Length of 8 SWG, galvanized iron= 300+2% for sag
=306mts
In weight =10 mts/kg=30.6kg
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
1
RCC poles (9 mts long)
6 nos
2
AAC, mans conductors of size(3/3.00mm)
1224
mts(70kg)
3
E arth conductors 8 SWG GI
306 mts
(30.6kg)
4
Shackle Insulators with ‘Dstraps i.e 4 on each
pole
24+4=28 nos
5
Nuts and Bolts 15 mm dia ,200 mm long with
washers for xing ‘Dstraps with pole,one for
each straps
28nos.
6
Nuts and Bolts 15 mm dia ,125 mm long with
washers for xing insulators with ‘Dstraps
28 nos.
7
Eye bolts,15 mm dia ,200 mm long for holding
earth wire on intermediate pole
4 nos.
Earth wire pole clamp one on each end pole
2 nos.
9
Guard wire of size 7/16 SWG ,for guarding at
approximate 15 places
30 mts
10
Aerial fuse,32 amp rang on last pole
3 nos.
11
L.T outdoor cable box, complete with clamps
2 nos.
12
Reel insulator
10 nos.
14
Stay wire set complete i.e 2 sets on each
terminals poles
2+2=4 nos
15
Earthing sets complete for earng
1 sets
16
Number plates with clamps
6 nos.
17
Pole foundaon for each pole
6 nos.
18
To complete the job miscellaneous items such
as cement ,sand, concrete etc
-
19
14 SWG ,galvanized steel wire as binding wire
2kg
Q.3 Esmate the quanty of material required for the construcon of 1 kilometre
overhead line. The line is tapped from the exisng 11 KV line to feed a parcular locality.
The parculars of the important materials to be used for the line to be erected are as
follows.
a) Size of conductor : ACSR 6/1 mm
b) Tubular pole or supports of 11 metres length
c) Size of earth wire : G.S (galvanized steel ) 8 SWG
d) Average span length=100 mts.
e) No. of earthing sets to be installed:3 nos.
Soluon
Total Length of conductors (ACSR weasel conductor 6/1 X 2.59 mm )= (1000X3)+2% for sag
=3000+60=3060 mts
Total length of G.I. earth wire of size 8 SWG =1000+2% for sag
=1000+20=1020 mts
Material Table
Si
no
.
descripon of materials with specicaons
Quant
y
1
Tubular line supports (11 mts long)
10 nos
2
Material required for connecon with exisng line
of 11 KV line
1. M.S channel for cross arm (10 cmX5
cmX1.5mts)
2. H.T ,11 KV Disc insulator with complete
ngs
3. H.T ,11 KV ,pin type insulators with nuts and
bolts
4. Stay complete sets ( clamps ,stay wire, egg
insulators ,stay rod stay bow, stay plates)
5. Earth wire clamp
6. Binding wires
7. Clamps for M.S channel
8. Concreng for stay rod
1no.
3nos.
2 nos.
2nos.
1no.
1 kg
1 no.
2nos.
3
Fing for new line supports
1. Stone pads for poles
2. Angle iron cross arms, 1 for each pole
3. clamps for xing cross arm with poles
4. 11 KV ,pin type insulators with nuts and
bolts
5. No. plates with clamps for xing
6. Danger plates with clamps for xing
7. Earth wire clamp
8. Barbed wire for an climbing for 10 poles @
1 kg
for each pole
9. Binding wires (for xing conductors over
insulators)
10. Stay complete sets ( clamps ,stay wire, egg
insulators ,stay rod stay bow, stay plates)
10 nos.
10 nos.
10 nos.
30 nos.
10 nos.
10 nos.
10 nos.
10kg
6kg
2nos
4
ACSR weasel conductors of size 6/1 X 2.59 mm
3060
mts
5
G.I earth wire of size 8 SWG
1020
mts.
6
Earthing complete sets (G.I pipe, charcoal ,salt etc)
3 nos.
7
Painng for poles
10 nos.
Q.4 Esmate the material and cost for the construcon of 1 kilometre overhead line. The
line is tapped from the exisng 11 KV overhead line. Assuming that the line is passing over
the main road, telegraph line and railway line. Given data:
a) Size of conductor : ACSR 6/1 mm gopher
b) Type of pole : R.S ( Rolled steel ) joist 10 mts and 11.5 metres long.
c) Size of earth wire : G.S (galvanized steel ) 8 SWG
d) Type of cross arm : mode of angle iron
e) No. of earthing : plate eathing
Soluon
Total Length of conductors (ACSR gopher conductor 6/1 X 2.36 mm )= (1000X3)+2% for sag
=3000+60=3060 mts
Total length of G.I. earth wire of size 8 SWG =1000+2% for sag
=1000+20=1020 mts
Material Table
Si
no
.
descripon of materials with specicaons
Quanty
1
a) R.S joist poles 15cm diameter 10 mt
long
b) R.S joist poles 15cm diameter 11.5 mt
long
6 nos.
6 nos.
2
Material required for connecon with exisng
line of 11 KV
a) M.S channel for cross arm (10 cmX5
cmX1.5mts)
b) H.T ,11 KV Disc insulator with complete
ngs
c) H.T ,11 KV ,pin type insulators with nuts
and bolts
d) Stay complete sets ( clamps ,stay wire,
egg insulators ,stay rod stay bow, stay
plates)
e) Earth wire clamp
f) Binding wires
g) Clamps for M.S channel
h) Concreng for stay rod
1no.
3nos.
2 nos.
2nos.
1no.
1 kg
1no.
2nos.
3
Fings for new line supports
a) Stone pads for poles
b) Angle iron cross arms, 1 for each pole
c) clamps for xing cross arm with poles
d) 11 KV ,pin type insulators with nuts and
bolts
e) No. plates with clamps for xing
f) Danger plates with clamps for xing
g) Earth wire clamp
h) Barbed wire for an climbing for 10
poles @ 1 kg
for each pole
i)Binding wires (for xing conductors over
insulators)
12 nos.
12 nos.
12nos.
42 nos.
12 nos.
12 nos.
12 nos.
12 kg
8 kg
4
Extra material for poles at road crossing
a) Brindling cross arm
b) Cross arm clamps
2 nos.
2nos.
c) Guard wire
d) Eye bolts for holding guard wire
25 kg
6 nos
5
Extra material for telegraph line crossing
a) Cross arm
b) Clamps for cross arm
c) Guard wire
d) Eye bolts for holding guard wire
2nos.
2 nos.
25 kg.
6 nos
6
Extra material for rail way line crossing
a) Cross arm
b) Clamps for cross arm
c) Guard wire
d) Eye bolts for holding guard wire
2nos.
2 nos.
25 kg.
6 nos
7
ACSR gopher conductors of size 6/1 X 2.36
mm
3060 mts
8
G.I earth wire of size 8 SWG
1020 mts.
9
Earthing complete sets (G.I pipe, charcoal
,salt etc)
4 nos.
10
Painng for poles
12 nos.
OVER HEAD SERVICE LINES
5. 1 Components of service lines, service line (cables and conductors), bearer wire, lacing rod.
Ariel fuse, service support, energy box and meters etc.
5. 2 Prepare and esmate for providing single phase supply of load of 5 KW (light, fan, socket)
to a single stored residenal building.
5. 3 Prepare and esmate for providing single phase supply load of 3KW to each oor of a
double stored building having separate energy meter.
5. 4 Prepare one esmate of materials required for service connecon to a factory building
with load within 15 KW using insulated wire.
5. 5 Prepare one esmate of materials required for service connecon to a factory building
with load within 15 KW using bare conductor and insulated wire combined.
CHAPTER -5 OVERHEAD SERVICE LINE
PREPARE AND ESTIMATE FOR PROVIDING SINGLE PHASE SUPPLY LOAD OF 5KW
(LIGHT,FAN,SOCKET) TO A SINGLE STORED RESIDENTIAL BUILDING
Q.1 A newly constructed single storeyed house is to be provided with single phase 230
volts,50 HZ having a load of 5 KW(light,fan,socket). The supply is to be given from overhead
line 20 mt. away from the building. Prepare a list of the material,for giving sevice
connecon and also esmate the cost of the service connecon. A G.I pipe is to be raised
along the roof to receive bare conductor on its cross arm ed with insulators. Also draw
sketch of service connecon.
Soluon
Assumpons
1. Height of ground oor=3.5 mts.
2. Service connecon received at the height of 6 mts. from ground.
Selecon and rang of weatherproof ,twin core, aluminium conductor cable and line
conductor
Total connected load=5 KW
Total load in ampere=5000/230=21.7 amp
Diversity factor=60%X21.7=13 amp
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building =(50%
X13)+13=19.5 amp
It is therefore suggested that
Rang of weatherproof cable =6 mm
2
or 1/2.80 mm ,twin core, PVC insulated cable to
carry a load current of 27 amp.
Rang of bare conductor for installaon between distribuon pole upto insulators=10
mm
2
,AAC
Rang of earth wire=8 SWG
Material Table
Si
no
.
Specicaon
Quanty
1
PVC weatherproof cable of size 6mm
2
or
1/2.80 mm twin core including wastage
10mts
2
AAC for phase and neutral connecon (10
mm
2
)
42 mts
3
8 SWG GI earth wire(from pole to meter
board)
20+1+10=3
1 mts
4
G I pipe (50 mm diameter)
8mt.
5
Conduit bends
3 nos
6
GI pipe Saddles
10 nos.
7
Earthing Thimble (to x earth wire and stay
wire)
2 nos.
8
LT shackle insulators
4 nos.
9
Angle iron bracket insulator of
size(50mmX50mmx6mmx60mm) long
2 nos.
10
Stay insulator
1no.
11
Stay wire
7mt.
12
Stay bow
1 nos
13
Stay rod
1 nos
14
Cement
1 bag
15
Sand
3 bag
16
Concrete
2 bag
17
2 Way juncon box
2 nos.
18
Nuts & bolts
2 pkt
Q.2 A newly constructed single storeyed house is to be provided with single phase 230
volts,50 HZ having a load of 4 KW. The supply is to be given from overhead line 30 mt. away
from the building. Prepare a list of the material,for giving sevice connecon and also
esmate the cost of the service connecon.
Soluon
Assumpons
3. Height of ground oor=3.5 mts.
4. Service connecon received at the height of 6 mts. from ground.
Selecon and rang of weatherproof ,twin core, aluminium conductor cable
Total connected load=4 KW
Total load in ampere=4000/230=17.29 amp
Diversity factor=60%X17.29=10.43 amp
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building =(50%
X10.43)+10.43=15.21 amp
It is therefore suggested that
Rang of weatherproof cable =4 mm
2
or 1/2.24 mm ,twin core, PVC insulated cable
Rang of G.I wire=8 SWG
Material Table
Si
no
.
specicaon
quanty
1
PVC weatherproof cable(from pole to EM
with wastage)
30+2+15=4
7 mt
2
8 SWG GI wire
32 mt.
3
G I pipe (50 mm diameter)
8mt.
4
Conduit bends
3 nos
5
GI pipe Saddles
10 nos.
6
Earthing Thimble
2 nos.
7
Stay wire
7mt.
8
Stay insulator
1 nos
9
Stay bow
1 nos
10
Stay rod
1 nos
11
Cement
1 bag
12
Sand
3 bag
13
Concrete
2 bag
14
2 Way juncon box
2 nos.
15
Nuts & bolts
2 pkt
16
Binding wire
2 mts
PREPARE AND ESTIMATE FOR PROVIDING SINGLE PHASE SUPPLY LOAD OF 3KW TO EACH
FLOOR OF A TO DOUBLE STORED RESIDENTIAL BUILDING HAVING SEPARATE ENERGY METER
Q.3 Prepare a list of material and esmate the cost for giving service connecon to a
double storeyed building having two energy meters.The supply is to be given at 230 volt
single phase having a load of 4 sub-cicuit (light,fan )and two 15 amp socket points on each
oor .The supply is to be given from overhead line 20 metres away from the building .Also
draw diagram of service connecon.
Soluon
Assumpons
1. Height of ground oor=3.5 mts.
2. Total height of rst oor from ground=7mts.
3. Service connecon received at the height of 6 mt. from ground.
4. Height of ground oor meter board from oor=1.5mts.
Selecon and rang of weatherproof ,twin core, aluminium conductor cable and Line
conductor
Total connected load for 4 sub-circuit=4X800=3200 was
2-15 amp sockets=2X1000=2000was
So total load of a single building storeyed=3200+2000=5200 wa
Total load in ampere=5200/230=22.6amp (for single storeyed )
Total connected load for both oor=22.6+22.6=45.2 amp
Diversity factor=60%X45.2=27.12amp
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building .It is therefore a
beer suggeson that a weather proof cable of higher rang may be used=(50%
X27.12)+27.12=40.68amp
It is therefore suggested that
Rang of weatherproof cable =16 mm
2
or 7/1.70 mm ,twin core, PVC insulated cable
Rang of bare conductor for installaon between distribuon pole upto insulators=16
mm
2
ACSR Conductor
Rang of G.I wire=8 SWG
Material Table
Si
no
.
Specicaon
Quanty
1
Shackle insulators with U clamps,nuts & bolts
2+2=4 nos.
2
Mild steel channel or hook
2 nos.
3
ACSR conductor for phase and neutral
connecon (16mm
2
) including wastage
20+20+2=42
mts
4
8 SWG GI earth wire(from pole to meter boa)
20+1+15=36
mts
5
MS angle iron bracket of
sze(50mmX50mmx6mmx1mt) long
2 nos.
6
PVC Weather proof cable
15 mt
7
MS Saddles
15 nos.
8
Earthing Thimble (to x earth wire )
2 nos.
9
Reel insulator
1no.
10
Guard wire
7mt.
11
Cement
1 bag
12
Sand
3 bag
13
2 Way juncon box
2 nos.
14
Nuts & bolts
2 pkt
PREPARE ONE ESTIMATE OF MATERIAL REQUIRED FOR SERVICE CONNECTION TO A
FACTORY BUILDING WITH LOAD WITHIN 15KW USING INSULATED WIRE
Q.1 A workshop required to connect a 3-phase 15 KW ,415 V ,50 HZ motor to a 3-phase ,4-
wire,415/240 volt ,50 HZ overhead line .The distance of the service line from the workshop
structure having motor is 15 mt. The motor has an eciency of 85% and a power factor of
0.8 . Esmate the quanty and cost of material required.
Soluon
Assumpons
1. Height of ground oor=6 mts.
2. Service connecon received at the height of 7 mts. from ground.
Selecon and rang of weatherproof ,twin core, aluminium conductor cable
Total connected load =15KW
Running current=


=30 amp
Starng current=1.5  amp
Diversity factor =60% 
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building =(50%
)+27=40.5 amp
It is therefore suggested that
Rang of weatherproof cable =10mm
2
or 1/3.55 mm ,4 core, PVC insulated aluminium
conductor
Rang of G.I wire=8 SWG
Material Table
Si
no
.
specicaon
quanty
1
PVC weatherproof cable(from pole to EM
with wastage)
15+2+5+10
=32mt
2
8 SWG GI wire
17 mt.
3
G I pipe (50 mm diameter)
7mt.
4
Conduit bends
3 nos
5
GI pipe Saddles
15 nos.
6
Pole clamp
1 nos
7
Cement
1 bag
8
Sand
3 bag
9
Concrete
2 bag
10
2 Way juncon box
2 nos.
11
Nuts & bolts
2 pkt
12
Binding wire
2 mts
13
M S hook
1 no.
Q.2 A workshop owner wants 3-phase ,4 wire power connecon to his 10 HP motor from
the pole of 400v ,3 phase 50 HZ overhead line at a distance of 200mt. from the workshop.
Make a sketch showing the arrangement of supply and esmate the quanty and cost of
the material required.
-
Soluon
Assumpons
1. Height of ground oor=6 mts.
2. Service connecon received at the height of 7 mts. from ground.
Selecon and rang of weatherproof ,twin core, aluminium conductor cable
Total connected load =10HP
Running current =


= 15.8 amp
Starng current=1.5  amp
To meet the present load requirement and Provision for future requirement in the event
expansion of building and any other electrical points in the exisng building =(50%
)+23.7=35.55 amp
It is therefore suggested that
Rang of weatherproof cable =6 mm
2
or 1/2.80 mm ,4 core, PVC insulated aluminium
conductor
Rang of bare conductor for installaon between distribuon pole upto insulators=10
mm
2
ACSR Conductor
Rang of G.I wire=8 SWG
Material Table
Si
no
.
specicaon
quanty
1
PVC weatherproof cable
15 mts
2
Bare conductors
808 mts
3
Shackle insulator
8 nos.
4
8 SWG GI wire
202 mt.
5
G I pipe (50 mm diameter)
6 mt.
6
Conduit bends
3 nos
7
GI pipe Saddles
15 nos.
8
Earthing Thimble
2 nos.
9
Cement
1 bag
10
Stay insulator
1no.
11
Stay wire
7mt.
12
Stay rod
1 nos
13
Stay bow
1 nos
14
Reel insulator
2no.
15
Guard wire
8mt.
16
Sand
3 bag
17
Concrete
2 bag
18
2 Way juncon box
2 nos.
19
Nuts & bolts
2 pkt
20
Binding wire
2 mts
ESTIMATING FOR DISTRIBUTION SUBSTATIONS
6. 1 Prepare one materials esmate for following types of transformer substaons.
6.1.1 Pole mounted substaon.
6.1.2 Plinth Mounted substaon.
CHAPTER -6 ESTIMATING FOR DISTRIBUTION SUBSTATION
Q.1 Esmate the cost of a pole mounted sub-staon of capacity 50 KVA transformer of
rang 11/0.4 KV. The H.T line is available about 50 metres from the proposed site.Also make
a neat sketch of the pole mounted sub-staon.
Soluon
Total Length of conductors (ACSR gopher conductor 6/1 X 2.36 mm )= (50X3)+2% for sag
=150+3=153 mts
Total length of G.I. earth wire of size 8 SWG =50+2% for sag
=50+1=51 mts.
Material Table
Si
no
.
descripon of materials with specicaons
Quant
y
1
Material for H.T connecon with main line
1. M.S channel cross arm 10 cm  1.5 mt
long
2. H.T ,11 KV Disc insulator with complete ngs
3. Stay complete sets ( clamps ,stay wire, egg
insulators ,stay rod stay bow, stay plates)
4. Earth wire clamp
5. Binding wires
6. Clamps for M.S channel
7. Concreng for stay rod
1no.
3nos.
2 nos.
2nos.
500
gms
1 no.
2nos.
2
Conductor ACSR gopher 6/12.36 mm diameter
153
mts.
3
Earth conductors 8 SWG GI
51 mts.
4
R .S joist 175 mm  10 mt long
2 nos.
5
Fings on H.T double pole structure for pole
mounted sub-staon.
1. Stone pad
2. Sub-staon plate
3. M.S channel cross arm 100 mm 
 2.65mt long
4. Eye bolt
5. Dropper angle iron 75 mm 
 2mt long
6. Stay complete sets
7. 11 KV ,Disc type insulators with nuts and bolts
8. Binding wires
11. No. plates with clamps for xing
12. Danger plates with clamps for xing
13. Earth wire clamp
14. Barbed wire
15. Earthing complete
16. Jumper wire for jumping
17. Nuts and bolts of size as required.
18. Concreng poles
19. T.P.M.O switch
20. Painng of pole and other aachments
21. Fuse sets
2 nos.
1 no.
1no.
3 nos.
6no.
4 nos.
3nos.
500
gms
1no.
1no.
1no.
5kg.
1set
11mts
18nos.
2 nos
1no.
2 litres
1set
6
Transformer 50 KVA ,11/0.4 KV
1no.
7
TPICN(triple pole iron clad with neutral ) main switch
100 ampere rang
1no.
8
Earthing for transformer
1no.
9
Lighng arresters one set of three
1set